Installation & Commissioning Guide PKY470-700 Tri-Capacity Package with CM100 Control
Doc. No.0525-032
Ver. 9 180921
SYSTEM COMPONENTS CONTROL MATRIX
System
Components
Control
Modes of Operation
Internal Sensors Mode
External Input Mode
Remote Demand Mode
Unit On / Off
Through CP05 / CP10
Through CP05 / CP10
Through CP05 / CP10
Compressors
Internally controlled
Through 24VAC External Inputs
or 0-10VDC Input
Through MODBUS / BACnet
Indoor Fans
Internally controlled
Can be Internal or External
0-10VDC Input, 24VAC
Through MODBUS / BACnet
Heat / Cool
Internally controlled
Through 24VAC Input
Through MODBUS / BACnet
Remote On / Off
Needs to be enabled through
Service menu
(Communication Configuration)
Volt free Digital Input
Needs to be enabled through
Service menu
(Communication Configuration)
Volt free Digital Input
Needs to be enabled through
Service menu
(Communication Configuration)
Volt free Digital Input
On / Off through BMS
(MODBUS/BACnet)
Needs to be enabled through
Service menu
(Communication Configuration)
Needs to be enabled through
Service menu
(Communication Configuration)
Needs to be enabled through
Service menu
(Communication Configuration)
NOTE:
Unit On
/
Off through CP05
/
CP10, Remote On
/
Off or BMS On
/
Off can be enabled at a time, the
priorities are set as per the table below:
Unit On / Off
(CP05 / CP10)
Remote On / Off
On / Off through BMS
Unit Status
ON
ON
ON
Unit On
ON
OFF
ON
Unit Off by DIN
ON
OFF
OFF
Unit Off by BMS
OFF
OFF
OFF
Unit Off by Key
OFF
ON
OFF
Unit On