ELECTRICAL
Step 3:
Attach the Lateral Sliding Plastic Brackets (one on each side) unto the Control Interface and push tight
against the mounting panel:
Control Interface as
mounted unto the panel
PUSH
Panel
Back Piece-
Control Interface
PUSH
2 x Lateral Sliding
Plastic Brackets
(1 each side)
Front Panel-
Control Interface
DATA CABLE AND RJ12 PLUG PREPARATIONS:
Option 1 - Data Cable with RJ12 plug at both end:
Prepare the Data Cable with RJ12 plugs to be connected to Control Interface and CM100 RJ12 receptacles.
(Keep the length of this cable no longer than the specified maximum cable length).
Refer the schematic below (seen from the cable end) for the wiring connection to RJ12 plugs.
VIEW FROM CABLE END
VIEW FROM CABLE END
RJ12 Plug
(
Installer to Provide
)
RJ12 Plug
(
Installer to Provide
)
6 Core Flat 7/0.12 (AWG28) Telephone Cable
50m Max. Length - Field Scope
(
Installer to Provide
)
6
5
4
3
2
1
6
5
4
3
2
1
RJ12 Plug
(
Installer to Provide
)
RJ12 Plug
(
Installer to Provide
)
VIEW FROM CABLE END
VIEW FROM CABLE END
6 Core (3 Pair) Twisted Pair 7/0.20 (AWG24) Shielded Data Cable
200 Max. Length - Field Scope
(
Installer to Provide
)
6
5
4
3
2
1
6
5
4
3
2
1
RJ12 Terminal Connections
• Terminal 1:- Connect to +Vdc on the connector block.
• Terminal 2:- Connect to GND on the connector block.
• Terminal 3:- Connect to RX-/TX- on the connector block.
• Terminal 4:- Connect to RX+/TX+ on the connector block.
• Terminal 5:- Connect to GND on the connector block.
• Terminal 6:- Connect to +Vdc on the connector block.
Twisted Pair
Twisted Pair
Twisted Pair