BANKING OF UNITS
END-TO-END CONFIGURATION
CLUSTER CONFIGURATION
NOTES :
1. Service Clearance and Airflow Allowances given above are suggested minimum based on the condition that the spaces around
the units are free from any obstructions and a walkway passage of 1000mm between the units or between the unit and the
outside perimeter is available.
PLEASE NOTE THAT UNDER ALL CIRCUMSTANCES, CONDENSER AIR MUST NOT
RECIRCULATE BACK ONTO CONDENSER COIL.
2. Minimum service access areas and spaces for airflow are responsibilities of the installer,
ActronAir
®
will not be held responsible for any extra charges incurred due to lack of access and space for airflow.
3. Do not scale drawing.
UNIT 1
1000 mm
SERVICE
CLEARANCE
(PLUG FAN)
+
UNIT 1
1000 mm
SERVICE
CLEARANCE
(COMP. & ELEC.)
+
UNIT 2
AIRFLOW
ALLOWANCE
UNIT 1
1000 mm
FILTER
ACCESS
UNIT 2
1000 mm
FILTER
ACCESS
UNIT 3
1000 mm
FILTER
ACCESS
UNIT 2 & 3
1000 mm
SERVICE
CLEARANCE
(PLUG FAN)
+
(COMP. & ELEC.)
DUCT
WORK
DUCT
WORK
DUCT
WORK
DUCT
WORK
DUCT
WORK
DUCT
WORK
UNIT 3
OUTDOOR COIL
OUTDOOR COIL
INDOOR COIL
PLUG
FAN
UNIT 2
OUTDOOR COIL
OUTDOOR COIL
INDOOR COIL
PLUG
FAN
UNIT 1
OUTDOOR COIL
OUTDOOR COIL
INDOOR COIL
HEIGHT CLEARANCE FOR ALL THE UNITS = 1500mm
PLUG
FAN
AIRFLOW ALLOWANCE
500 mm
AIRFLOW
ALLOW
ANCE
500 mm
AIRFLOW ALLOWANCE
500 mm
AIRFLOW ALLOWANCE
500 mm
AIRFLOW
ALLOW
ANCE
500 mm
KEEP ALL CLEARANCES FREE
OF ANY OBSTRUCTIONS
UNIT 2
1000 mm
SERVICE
CLEARANCE
(COMP. & ELEC.)
+
(PLUG FAN)
+
UNIT 1
AIRFLOW
ALLOWANCE
UNIT 1
1000 mm
SERVICE
CLEARANCE
(PLUG FAN)
UNIT 1
1000 mm
SERVICE
CLEARANCE
(COMP. & ELEC.)
UNIT 2
1000 mm
FILTER
ACCESS
DUCT WORK
DUCT
WORK
DUCT WORK
DUCT
WORK
UNIT 3
1000 mm
SERVICE
CLEARANCE
(PLUG FAN)
UNIT 3
1000 mm
SERVICE
CLEARANCE
(COMP. & ELEC.)
UNIT
3
1000 mm
FIL
TER
ACCESS
UNIT
1
1000 mm
FIL
TER
ACCESS
UNIT
2
&
UNIT
3
500 mm
AIRFLOW
ALLOW
ANCE
DUCT WORK
DUCT WORK
UNIT 1
OUTDOOR COIL
OUTDOOR COIL
INDOOR COIL
PLUG
FAN
UNIT 3
OUTDOOR COIL
OUTDOOR COIL
INDOOR COIL
PLUG
FAN
UNIT 2
OUTDOOR COIL
OUTDOOR COIL
INDOOR COIL
PLUG
FAN
HEIGHT CLEARANCE FOR ALL THE UNITS = 1500mm
AIRFLOW ALLOWANCE
500 mm
AIRFLOW ALLOWANCE
500 mm
AIRFLOW ALLOWANCE
500 mm
KEEP ALL CLEARANCES FREE