1.1 Optional BMS (Remote Demand) Mode
To configure the system’s control operation for BMS (Remote Demand) Mode, make sure:
• that you have connected the required supply to Multi Input 1 & 2, the stage inputs to Stage 1, 2, 3 and Heat
Inputs in the control box and the BMS Interface Card (ICMOD-485).
•
that you have configured the required Compressors and Indoor Fans modes of operation.
• that the
Room Air Temperature Sensor is connected to the unit
.
Configuration Procedure:
1.1.1
Set the unit control mode to “Remote Demand” via Service menu:
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc11
Unit control mode :
REMOTE DEMAND
Supply Fan Control :
Select Wall Control:
SINGLE CL01
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc11. S. Configuration
Change to
“
REMOTE DEMAND
”
NOTE:
Service settings and Communicate config. under Thermoregulation menu are password protected. Enter
the Service Password (7378) in order to access these screens.
1.1.2
In service menu, go to communicate config screen and set the protocol to “MODBUS”.
Display Progression:
G. Service
F. Data logger
Main Menu G
H. Manufacturer
Service menu Ge
c. Unit switch
e. Communicate config.
d. Working log
BMS
config. Ge1
Address: 1
Protocol : MODBUS
Speed : 19200
G. Service
Ge. Comm config
Ge1. BMS config.
Ensure Protocol is set
as “
MODBUS
”
1.1.3
Make sure the option for the BMS to turn the unit On / Off is Enabled:
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Ge
c. Unit switch
e. Communicate Config.
d. Working log
Bms Config. Ge2
Enable the BMS to turn
the unit On / Off : Yes
On loss of Comms :
TURN OFF
G. Service
Ge. Comm config
Ge2 BMS Config.
Set to “
Yes
” in order to
enable the option for BMS
to turn the unit On / Off
SETTING UP BMS (REMOTE DEMAND) OPTION