36
Installation & Commissioning Guide PKY470-700 Tri-Capacity Package with CM100 Control
Doc. No.0525-032
Ver. 9 180921
COMPRESSORS AND INDOOR FANS MODES OF OPERATION
Configuration Procedure:
(Follow these procedures to revert back to Internal Control mode from other Compressors modes of operation).
3.1.1
Set the unit control mode to “Internal Sensors” via Service menu:
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc11
Unit control mode :
INTERNAL SENSORS
Supply Fan Control :
Select Wall Control:
SINGLE CL01
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc11. S. Configuration
Change to
“
INTERNAL SENSORS
”
NOTE:
Service settings and Communicate config. under Thermoregulation menu are password protected. Enter
the Service Password (7378) in order to access these screens.
3.1.2
In service menu, go to communicate config sub-menu and set the protocol to “Carel”.
Display Progression:
G. Service
F. Data logger
Main Menu G
H. Manufacturer
Service menu Ge
c. Unit switch
e. Communicate config.
d. Working log
BMS
config. Ge1
Address: 1
Protocol : CAREL
Speed : 19200
G. Service
Ge. Comm config
Ge1. BMS config.
Ensure Protocol is set
as “
CAREL
”
3.1.3
Make sure the option for the BMS to turn the unit On / Off is disabled:
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Ge
c. Unit switch
e. Communicate Config.
d. Working log
Bms Config. Ge2
Enable the BMS to turn
the unit On / Off : No
On loss of Comms :
TURN OFF
G. Service
Ge. Comm config
Ge2. BMS Config.
Set to “
No
” in order to
disable the option for BMS
to turn the unit On / Off
3.1.4
Make sure the Multi Input assigned to the Compressors via S.Configuration screen
Gfc8
is disabled:
NOTES:
◦
Disable Multi Input 2 (U12) for Compressors.
◦
Otherwise, disable Multi Input 1 (U11) for Compressors in units with "W - 3 Phase Sequence Relay Option",
which should be the multi input for the Compressors with this option. Do not disable Multi Input 2 when used
for "W - 3 Phase Sequence Relay Option".
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc8
Sensor present :
Multi Input 1 : NO
Multi Input 2 : NO
Change the required
Multi Input to “
NO
”
NOTE: The Compressors are now configured/ready to be controlled through ActronAir Internal Control.
3.2 Compressors 0-10VDC External Control Mode
In this mode, the Compressors can be controlled through 0-10VDC input from the external controller and all
the logic will be run by the external controller.
Configuration Procedure:
3.2.1
Change the mode of operation to “External Input” via Service menu:
Change to
“
EXTERNAL INPUT
”
Display Progression:
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
S. Configuration Gfc11
Unit control mode :
EXTERNAL INPUT
Supply Fan Control :
Select Wall Control:
SINGLE CL01
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc11. S. Configuration
NOTE:
Service settings and Communicate config. under Thermoregulation menu are password protected. Enter
the Service Password (7378) in order to access these screens.