22
Installation & Commissioning Guide PKY470-700 Tri-Capacity Package with CM100 Control
Doc. No.0525-032
Ver. 9 180921
WIRING DIAGRAM MATRIX
Model
Wiring Diagram
PKY470T-6Q2
0515-8200
PKY540T-6Q2
0515-8200
PKY620T-6Q2
0515-8600
PKY700T-6Q2
0515-8600
ELECTRICAL
CIRCUIT BREAKER SIZE & CABLE SIZE
Model
Circuit Breaker
Size
Cable Size
*
(mm
2
)
Amps
MAIN
(4 Core + E)
PKY470T-6Q2
50.0
10.0
PKY540T-6Q2
50.0
10.0
PKY620T-6Q2
63.0
16.0
PKY700T-6Q2
80.0
25.0
* Suggested Minimum Cable Size should be used as a guide only,
refer to AS/NZS 3000 “Australian / New Zealand Wiring Rules” for more details.
A
B
PACKAGE ELECTRICAL CONNECTION
WALL
CONTROLLER
(Optional)
CIRCUIT BREAKER
(Field Supplied)
SUB-MAIN
TO UNIT
PACKAGE
UNIT
B
A
6 Core (3 Pair) Twisted Pair
7/0.20 (AWG24)
Shielded Data Cable
(
Installer to Provide
)
or
6 Core Flat
7/0.12 (AWG28)
Telephone Cable
(
Installer to Provide
)
LOW VOLTAGE MAINS WIRING
(415 VAC)
EXTRA LOW VOLTAGE DATA CONTROL WIRING
(24 VAC)
•
All electrical work must be carried out by a qualified technician.
• Make sure all wiring is in accordance with local wiring rules.
• Wiring connections should be made in accordance with the provided wiring diagram.
NOTE
: Unit wiring diagram is located in the Access Panel - Electrical.
IMPORTANT ELECTRICAL NOTES