52
Installation & Commissioning Guide PKY470-700 Tri-Capacity Package with CM100 Control
Doc. No.0525-032
Ver. 9 180921
ROOM AIR TEMP. SENSOR INSTALLATION / ADJUSTMENT
AVERAGING ROOM AIR TEMPERATURE SENSORS:
ROOM TEMP
NTC SENSOR 3
ROOM TEMP
NTC SENSOR 4
ROOM TEMP
NTC SENSOR 1
ROOM TEMP
NTC SENSOR 2
TERMINALS
18
AFTER HOURS
17
RTN AIR SENSOR
16
RTN AIR SENSOR (GND)
15
MULTI INPUT 2
14
COMMON (GND)
13
MULTI INPUT 1
12
SENSOR ADJUSTMENT INSTRUCTIONS:
1. Read the room air temperature from the control interface (the installed Room Air Temperature Sensor
is measuring the room air temperature).
2. Using a different temperature measuring device, measure the actual air temperature next to installed
Room Air Temperature Sensor.
3. Get the difference to adjust the installed Room Air Temperature Sensor via service menu:
Display Progression
G. Service
F. Alarm History
Main Menu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfb
a. Working hour set
b. Probe adjustment
c. Thermoregulation
Calibration Gfb1
Room Temp cal :
0.0
o
C
G. Service
Gf. Service settings
Gfb. Probe adjustment
Gfb1. Calibration
Example: If the actual measured room temperature is
2.0
o
C
higher or lower than control interface reading,
then adjust the offset to +2.0
o
C or -2.0
o
C coresspondingly.
Room Temp cal : +2.0
o
C
Calibration 01
Probe Adjustment Display
Enter
room air temp.
offset here
SPECIFICATIONS - SENSOR LEAD WIRE:
Distance
Item
up to 50m
up to 100m
NTC (Sensor Wire)
*
0.5mm
2
1.0mm
2
*
For compliance with EMC requirements, connect screen wire to Terminal 22 on the Outdoor Panel.
Use only the provided ActronAir duct bead sensor or the optional wall sensor.
Use of 3rd party sensors are not allowed as they are not tested with ActronAir air conditioning unit.
Room Temp cal : - 2.0
o
C
Calibration 01
Enter
room air temp.
offset here