ROOM AIR TEMP. SENSOR INSTALLATION / ADJUSTMENT
INTRODUCTION
The Room Air Temperature Sensor location varies and is specific on each individual site installation requirements,
hence the sensor is not fitted to your air conditioning unit. It is supplied and packed together with this installation guide
inside the Installation Guide / Warranty Pack envelope. The Room Air Temperature Sensor comes standard with 6m lead
wire, which can be extended for longer installation requirement. It will need installation and adjustment by the installer
prior to commissioning of your air conditioning unit.
INSTALLATION INSTRUCTIONS:
1. Install the Room Air Temperature Sensor on the return air duct or inside the room, just below the return air grille.
2. Ensure that the sensor is located where the room air is not affected by other heat source.
3. The Room Air Temperature Sensor must be properly secured in the chosen location.
4. Sensor wire should be routed securely and not to be exposed to sunlight, rain, dust and other contaminants.
5. Keep sensor wire away from high voltage cables.
INSTALLATION - SENSOR CONNECTION TO OUTDOOR TERMINALS (DEFAULT):
1. Cut the cable of the Room Air Temperature Sensor as close as possible to the plug:
2. Strip the cable to expose the wires:
Strip the cable to expose
the wires
Room Air
Temperature Sensor
3. Connect the sensor wires to the Outdoor Terminals:
TO
CM100
14
15
16
17
Connect sensor to
terminals # 16 & 17
Room Air
Temperature
Sensor
RTN AIR SENSOR
TERMINALS
COMMON (GND)
RTN AIR SENSOR (GND)
4. Room Temperature Sensor Screen
Display Progression
G. Service
F. Alarm History
Main Meu G
H. Manufacturer
Service menu Gf
d. Working log
f. Service settings
e. Communicate config.
Service menu Gfc
a. Working hour set
c. Thermoregulation
b. Probe adjustment
Thermoregulation Gfc2
Room Temperature
use OUTDOOR sensor
Probe weight value : 0
Room Temp. : 22.3
o
c
Wall Cont Temp. : 0.0
o
c
Control Value : 22.3
o
c
G. Service
Gf. Service settings
Gfc. Thermoregulation
Gfc2. Thermoregulation
Change setting from
“
INDOOR sensor
” to
“
OUTDOOR sensor
”
NOTES:
•
A Tri-Capacity of split configuration was used for the example above. A Tri-Capacity package configuration
would not display “use OUTDOOR/INDOOR sensor” and remain blank.
• The supplied Room Air Temperature Sensor is a Duct Bead type sensor (ActronAir Part No: 2060-036). A wall
type sensor is also available as an option (ActronAir Part Number LM-RS).
• For longer installation requirements, it is possible to extend the provided 6m sensor lead wire with an
extension wire. The extension wire
MUST
comply to the specifications on page 51 and the installer is required
to adjust the sensor to get proper reading.