Instructions describe below are applicable to Tri-Capacity models
with controller software Version 2021-136-2003 and onwards.
IMPORT ANT NOTE
Four Combinations of Room Air Temperature Sensor / After Hour Button Connections :
1.
No
Room Air Temperature Sensor (2060-036 or LM-RS) and After Hour Button are connected, since only the CL01
Control Interface built-in sensor is used to sense the room air temperature:
Jumper (Factory Installed)
AFTER HOURS
18
RTN AIR SENSOR (GND)
16
RTN AIR SENSOR
17
TERMINALS
2.
Normal
Room Air Temperature Sensor connection with no After Hour function required
.
Jumper (Factory Installed)
Room Air Temperature Sensor
AFTER HOURS
18
RTN AIR SENSOR (GND)
16
RTN AIR SENSOR
17
TERMINALS
3.
Replacing the Jumper (Factory Installed) with normally closed A/H Button when
After Hour function is required
.
A/H Button (normally closed contact)
Room Air Temperature Sensor
AFTER HOURS
18
RTN AIR SENSOR (GND)
16
RTN AIR SENSOR
17
TERMINALS
4.
No
Room Air Temperature Sensor (2060-036 or LM-RS) is connected to the Indoor Unit, since only the CL01
Control Interface built-in sensor is used to sense the room air temperature, and when After Hour function required
.
Jumper
A/H Button (normally closed contact)
AFTER HOURS
18
RTN AIR SENSOR (GND)
16
RTN AIR SENSOR
17
TERMINALS
Operational Logic:
A.
If the Timeclock (scheduler) is enabled via the Control Interface (CL01, CP05 or CP10) is “
Enabled
” and there
is currently an “
Active Event
”, the unit will “
Run Normal
” from start to the end of the event when the unit is
Turned-On. However,
a. If the Control Interface CL01 “ON/OFF” Button is pressed during the event time, the unit will Turn-Off, the event
(1 or 2) will be masked for the day only and will be active for the next scheduler’s round in the following week.
b. If the After Hour function is “
Enabled
” via Control Interface CL01 (menu 05) and when the “ON/OFF” Button is
pressed, the After Hour will start to time-out for a settable period 0.5, 1.0, 1.5 or 2.0 hours.
a. If the Control Interface CL01 “ON/OFF” Button is pressed while the After Hour is active, the unit Turn-Off.
Pressing the “ON / OFF” Button again will start another After Hour period, if there is no active event.
B.
If the unit is Turned-On via Control Interface (Cp05 or CP10) and the After Hour function is “
Disabled
” via Control
Interface CL01 (menu 05) and the Timeclock (scheduler) is “ON” with no active event, pressing the Control Interface
CL0
AFTER HOURS LOGIC WITH TIMECLOCK (SCHEDULER)