L1, L2, L3
3
Contactor
Supply
(e.g. 230VAC)
K1
k1
DOC DO0
DO1
DO2
24VDC
10 11
24VDC
DO3
DI0 DI1 DI2 DI3 DI4 DI5
UMC100
UMC-
PAN
Comm.
Interface
0V
I
Lim
Fwd
Stop
k1
GND
(24VDC)
M
3
3
24VDC
0V
2
VI15x
F1
Supply
0V/24V
Control Function Direct Starter (DOL)
Use this function in a feeder that requires a motor to start/stop in one direction of rotation.
• Relay output DO0 is used from the control function.
• Optionally DI0 can be used for contactor checkback supervision
• Optionally DI4/DI5 can be used to start/stop the motor locally
• Optionally DO2 or DO3 can be used as fault output
The following diagram shows the UMC wired for DOL operation. A signal lamp is connected to DO3 which serves as a fault output.
The main contactor is connected to DO0. An auxiliary contact of K is used by contactor checkback monitoring. The motor can be
started locally via DI4 and stopped via DI5. The remaining digital inputs can be freely used.
—
Circuit diagram of the UMC to control a motor in one direction of rotation. The checkback
contact k1 is optional
74
U MC10 0. 3 U N IVE R SA L MOTOR CONTROLLE R
T EC H N I C A L D E S C R I P T I O N