Parameter
Number
Parameter
Name
Description, Explanations
Options
Adjustable via
177 - 181
Param To PV
1 ... 5
Defines which analog value is sent cyclically via analog monitoring
word 0 ... 5
Value
Number
Current [%]
1
Thermal load [%]
2
Max Value (TTT and Time To Restart from FB Number of starts)
[s]
3
TTC [s]
4
Scaled Active Power (scaled with Power Scale Factor)
5
Max Motor Current At Startup [%]
6
Real Motor Startup Time [0,1s]
7
Motor Current At Trip [%]
8
Current unbalance [%]
9
Frequency (Current or Voltage) [0,1Hz]
10
PTC value [Ohm]
11
Earth Fault [%]
12
Number Of Starts
13
Number Of Trips
14
Number Of Thermal Trips
15
Number Of Emergency Starts
16
Number Of Starts Left (from FB Number of starts)
17
Voltage U
L1L2
[V] / U
L1N
[V] in single phase mode
18
Voltage U
L2L3
[V]
19
Voltage U
L3L1
[V]
20
Average Voltage [V]
21
Power Factor [0,001%]
22
Scaled Apparent Power (scaled with Power Scale Factor)
23
Voltage Unbalance [0,1%]
24
Voltage THD L1 [0,1%]
25
Voltage THD L2 [0,1%]
26
Voltage THD L3 [0,1%]
27
AM1 Analog Value Channel 1 (K or raw value 0…xxxx)
28
AM1 Analog Value Channel 2
29
AM1 Analog Value Channel 3
30
AM1 Max Temperature [K]
31
AM2 Analog Value Channel 1 (K or raw value 0…xxxx)
32
AM2 Analog Value Channel 2
33
AM2 Analog Value Channel 3
34
AM2 Max Temperature [K]
35
Current L1 [%]
36
Current L2 [%]
37
Current L3 [%]
38
Motor operation time [days]
39
Motor standstill time [days]
40
Average Current
[A, 0.1A, mA, as configured
in the custom application editior]
41
Current L1
42
Current L2
43
Current L3
44
Reserved
45 - 255
0 ... 255
Numbers 1 ... 5 are
transmitted in the analog
monitoring words by
default.
All
Communication Parameters Continued
131
PA R A M E T ER S A N D DATA S T R U C T U R E S O N A FI EL D B US
Содержание UMC100.3
Страница 1: ... MANUAL Univeral Motor Controller UMC100 3 ...