Digital Inputs DX111-FBP.0
Number of digital inputs
8 externally supplied, isolated inputs
Type 1 accord. to EN 61131-2
1DI0 ... 1DI4 with common root 1DIZ
2DI5 ... 2DI7 with common root 2DIZ
Supply for digital inputs
24 V DC
Isolation
Yes
Input signal bounce suppression
Typ. 6 ms
Signal 0 range including ripple
-31.2 ... +5 V
Signal 1 range including ripple
+15 ... +31.2 V
Input current per channel (24 V DC)
Typ. 6.0 mA
Input resistor to 0 V
3.9 k Ω
Cable length
unshielded max. 600 m
shielded max. 1000 m
Digital Inputs DX122-FBP.0
Number of digital inputs
8 externally supplied, isolated inputs
Type 2 accord. to EN 61131-2
1DI0 ... 1DI4 with common root 1DIZ
2DI5 ... 2DI7 with common root 2DIZ
Supply for digital inputs
110 V AC - 240 V AC
Isolation
Yes
Input signal bounce suppression
Typ. 20 ms
Signal 0 range including ripple
0 ... 40 V AC
Signal 1 range including ripple
74 ... 265 V AC
Frequency range
45 ... 65 Hz
Input current per channel (230V AC)
Typ. 10 mA
Analog Output
Type of connection
2-wire connection to display e.g. the motor current on an analogue meter.
Configurable output range
0-10 mA, 0/4 mA - 20 mA, 0-10 V
Cable shielding
Recommended for up to 30 m and outside the switchgear cabinet; shielding
mandatory for cables over 30 m
Max. output voltage
10 V
Accuracy
< 5%
Max. output load
500
Ω (if configured as current output)
Min. output load
1 k
Ω (if configured as voltage output)
Resolution
8 bit
Short-circuit-proof
Yes
Open-wire detection
Short-circuit detection
Yes, if configured as 0/4-20 mA output
Yes, if configured as 0-10V output
Isolation
No