Parameter
Number
Parameter
Name
Description, Explanations
Options
Adjustable via
Phases
42
Phase loss
protection
Trips the motor depending of the trip class within
1.5 -12
seconds
in case of a phase loss. This parameter must be set to On during
regular operation.
Off (0), On (1)
Note: If the voltage module
is present this parameter
activates both voltage and
current based phase loss
detection.
All
43
Curr Imb Trip
Level
Phase imbalance (current) trip threshold. Above this value a trip is
generated. This function is activated together with the phase
loss protection.
0...100%
Default value: 50
All excluding
GSD-PDQ22
44
Curr Imb Warn
Level
Phase imbalance (current) warning threshold. Above this value a
warning is generated. This function is activated together with the
phase loss protection.
0...100%
All excluding
GSD-PDQ22
45
Phase
reversal
If enabled the three phases must be fed through the UMC CTs in
the correct order (L1 left, L2 middle, L3 right).
L1L2L3 (0),
L3L2L1 (1)
Note: If the voltage module
is present this parameter must
not be changed.
All excluding
GSD-PDQ22
46
Check phase
sequence
Enables supervision of phase sequence (L1/L2/L3)
Disabled (0),
Trip (1),
Warning (2)
Note: If the voltage module
is present this parameter
activates both voltage and
current based phase sequence
protection.
All excluding
GSD-PDQ22
Over - and Undercurrent
32
Low curr trip
level
Value in % of I/I
e
. Below this value a trip is generated. A value of
0% disables the trip.
0...100% in steps of 5%
Default: 0%
0% disables the function
Unscaled: 0 ... 20
Example: 10 means 50%
All
34
Low curr warn
level
Value in % of I/I
e
. Below this value a warning is generated. A value
of 0% disables the warning.
0...100% in steps of 5%
Default: 50%
0% disables the function
Unscaled: 0...20
Example: 10 means 50%
All
33
Low curr trip
delay
Delay time until a low current trip is triggered.
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
35
Low curr warn
delay
Delay time until a low current warning is triggered.
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
36
High curr trip
level
Value in % of I/I
e
. Above this value a trip is generated. A value of
800% (160) disables the trip.
100...800 in steps of 5%
Default: 800%
800% disables the function
Unscaled: 20...160
Example: 100 means 500%
(100% is nominal current)
All
38
High curr warn
level
Value in % of I/I
e
. Above this value a warning is generated. A value
of 800% (160) disables the warning
100...800% in steps of 5%.
Default value is 150%.
800% disables the function
Unscaled: 20...160
Example: 100 means 500%
(100% is nominal current)
All
37
High curr trip
delay
Delay time until a high current trip is triggered..
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
39
High curr warn
delay
Delay time until a high current warning is triggered.
0...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 0...255
Example: 20 means 2s
All excluding
GSD-PDQ22
Protection Parameters Continued
128
U MC10 0. 3 U N IVE R SA L MOTOR CONTROLLE R
T EC H N I C A L D E S C R I P T I O N