![ABB UMC100.3 Скачать руководство пользователя страница 130](http://html.mh-extra.com/html/abb/umc100-3/umc100-3_manual_2876130.webp)
Communication Parameters
Parameter
Number
Parameter
Name
Description, Explanations
Options
Adjustable via
17
Address check
Enable check if bus address stored in the UMC is the same as the
one stored in the communication interface.
Off (0), On (1)
All
18
Busfault
reaction
UMC behaviour in the event of a bus fault.
Motor Off (0)
,
Retain (1),
Start For (2),
Start Rev (3)
All
-
Bus
address
Fieldbus address. Depending on the communication
interface used, the permitted address range is smaller
than the one allowed here.
0,1,2,3 ...255
UMC100-PAN
PBDTM
-
Parameter lock
Prevents any parameter changes if set to On.
Unlocked (0), Locked (1)
UMC100-PAN
-
I/O Data profile
Set length of I/O data
Profile 1, Profile 2
UMC100-PAN
-
DeviceNet
baudrate
Baudrate used if connected via DNP31 into a DeviceNet network
Autobaud (0)
125 kBaud (1)
250 kBaud (2)
500 kBaud (3)
UMC100-PAN
-
MODBUS
baudrate
Baud rate used if connected via MRP31 to a Modbus RTU network
1200 Baud (0)
2400 Baud (1)
4800 Baud (2)
9600 Baud (3)
19200 Baud (4)
57600 Baud (5)
UMC100-PAN
-
MODBUS Frame
Frame type used if UMC is connected via MRP31 to a
Modbus RTU network (number of data bits, parity, number
of stop bits)
Note: older versions of UMC100/UMC100.3 do not send
this parameter, then an autodetection function is active
8 Data, even, 1 Stop (1)
8 Data, odd, 1 Stop (2)
8 Data, no, 2 Stop (3)
8 Data, no, 1 Stop (4)
UMC100-PAN
-
MODBUS bus
timeout
The master has to send a telegram within the given time
otherwise the UMC triggers the configured busfault reaction.
0 (off) ... 255s
UMC100-PAN
-
IP setting mode
Mode how the IP address settings are made
Note: in Basic Mode the IP address is created automatically as
192.168.0.xxx where (xxx = set by “Bus Address”
Parameter)
DHCP (0)
Basic (1)
User defined (2)
UMC100-PAN
-
IP address, octet
1..4
IP address used if connected via Ethernet communication module to
Ethernet network
0..255
Default: 192.168.0.1
UMC100-PAN
-
Subnet mask,
octet 1..4
Subnet mask used if connected via Ethernet communication module
to Ethernet network
0..255
Default: 255.255.255.0
UMC100-PAN
-
Gateway, octet
1..4
Gateway-IP address used if connected via Ethernet communication
module to Ethernet network
0..255
Default: 0.0.0.0
UMC100-PAN
-
Enable
Webserver
Enable/Disable webserver when connected to an Ethernet network
Off (0)
On(1)
UMC100-PAN
-
Retrofit
To set UMC100.3 to UMC100-FBP.0 mode for backward compatibilty
Off (0)
UMC100-FBP (1)
UMC100-PAN
130
U MC10 0. 3 U N IVE R SA L MOTOR CONTROLLE R
T EC H N I C A L D E S C R I P T I O N