Parameter
Number
Parameter
Name
Description, Explanations
Options
Adjustable via
Voltage Dip / Load Shedding
142
Dip Enable
Enable / Disable function
Off (0)
,
On (1),
On + Rapid Cycle Lockout (2)
UMC100-PAN
PBDTM
143
Voltage Dip
Duration
Max. voltage dip duration time before a trip is signalled.
0.1...25.5s in steps of 0.1s
Default: 0.5s
Unscaled: 1...255
Example: 5 means 0.5s
All excluding
GSD-PDQ22
144
Autorestart
Window
If the voltage dip ends within this time window an autorestart is
triggered (if enabled).
0.1 ... 1s in steps of 0.1s
Unscaled: 1...10
Example: 5 means 0.5s
UMC100-PAN
PBDTM
145
Autorestart
Delay
Delay until the motor is restarted
0 ... 255s
UMC100-PAN
PBDTM
147
Enable
Autorestart
Enables the autorestart of the motor after end of the voltage dip
Off (0)
On (1)
UMC100-PAN
PBDTM
156
Dip Restart
Level
Voltage level indicating the end of the low voltage situation
50 ... 115% of U
e
in steps of 1%
Default value: 90
157
Dip Level
Voltage level indicating a low voltage situation and triggering the
DIP logic.
50 ... 115% of U
e
in steps of 1%
Default value: 70
Internal Ground Fault
10
Earth Flt Trip
Level
Above this ground fault current a ground fault tip is triggered.
A value of 255 % disables the trip.
20 ... 80 in % of nominal current
I
e1,2
(255 = off)
Default value is 255
Example: Ie = 100A, Earth Flt
Trip Level = 35%. Then a earth
fault current of 35A triggers a
trip.
All
11
Earth Flt Trip
Delay
Delay time until a ground fault trip is triggered.
Trip happens after the configured delay time plus a internal
calculation time of about 600ms.
0...25.5s in steps of 0.1s
Default: 0,5s
Unscaled: 0...255
Example: 20 means 2s
All
12
Earth Flt Warn
Level
Above this ground fault current a ground fault warning is
triggered.
A value of 255% disables the warning.
20 ... 80 in % of nominal current
I
e1,2
(255 = off)
Default value is 255
All excluding GSD
PDQ22
13
Earth Flt Warn
Delay
Delay time until a ground fault warning is triggered.
Warning happens after the configured delay time plus a internal
calculation time of about 600ms.
0...25.5s in steps of 0.1s
Default: 0,5s
Unscaled: 0...255
Example: 20 means 2s
All excluding GSD
PDQ22
16
Earth Flt
Detection
Mode of internal ground fault protection: Defines when the
internal ground fault protection is active.
Always (0)
After Startup (1)
All
Protection Parameters Continued
129
PA R A M E T ER S A N D DATA S T R U C T U R E S O N A FI EL D B US