![ABB UMC100.3 Скачать руководство пользователя страница 154](http://html.mh-extra.com/html/abb/umc100-3/umc100-3_manual_2876154.webp)
Analog Inputs
Number of inputs
3 (one AI111.0) / 6 (two AI111.0)
Type of analog inputs (adjustable)
0/4 mA - 20 mA / 0-10 V
Resolution
15 Bit
Meausuring ranges
0…20 mA and 0…10 V
0 …. 27648 dec (6C00 hex)
4…20 mA
0 …. 27648 dec (6C00 hex)
Max. input current for 0/4-20mA
60 mA (destruction limit)
Accuracy at 20°C (T20)
±1 % from full scale value
Temperature coefficient
0.05 / K deviation from T20
Input resistance
m
300 Ohm at 0/4 -20mA
M
10kOhm at 0-10V
Wire break detection
In operation mode: 4 mA - 20 mA
Cable shielding
Recommended for up to 30 m and outside the switchgear cabinet; shielding
mandatory for cables over 30 m
EMC UMC100.3, AI111.0, DX1xx-FBP.0 and VI15x-FBP.0
Measurement of radiated and conducted interference according to
EN61131-2 CISPR16-2-3
Class A
Notice:
This product has been designed for environment A.
Use of this product in environment B may cause
unwanted electromagnetic disturbances in which
case the user may be required to take adequate
mitigation measures.
Electrostatic discharge accoring to IEC 61000-6-2
8 kV air discharge
6 kV contact discharge
Radiofrequency electromagnetic field according to IEC 61000-4-3
10 V/m
Fast transient bursts according to EN61000-4-4
2 kV power supply
High energy surges according to EN61000-4-5
1SAJ530000R1***: 2/1 kv CM/DM
Others: 1/0.5 kV CM/DM
Conducted radio frequency interference according to EN61000-4-6
10 V
VI15x-FBP.0
High energy surges according to EN61000-4-5
1/0.5 kV CM/DM power supply
2/1 kV CM/DM L1/L2/L3 voltage inputs
Damped oscillatory wave acc. to
EN61000-4-18
Only voltage inputs L1/L2/L3:
2.5 kV / 1 kV CM / DM
Immunity low frequency harmonics acc. to EN61000-4-11
Power supply: 50 ... 12 kHz, 3 V
154
U MC10 0. 3 U N IVE R SA L MOTOR CONTROLLE R
T EC H N I C A L D E S C R I P T I O N
Содержание UMC100.3
Страница 1: ... MANUAL Univeral Motor Controller UMC100 3 ...
Страница 159: ...159 ...