![ABB UMC100.3 Скачать руководство пользователя страница 137](http://html.mh-extra.com/html/abb/umc100-3/umc100-3_manual_2876137.webp)
Function Block Related Parameters
Aux Input Block
In the standard built-in applications the inputs of this function block are connected to the digital inputs of the DX1xx module (see
section 'Using Expansion Modules').
Parameter
Number
Parameter Name
Description, Explanation
Options
Adjustable via
51 - 56
Aux inp 1-6 ack mode
Definition of the fault reset behavior
Manual Reset (0)
Auto Reset (1)
All
57 - 61
Aux Inp 1-6 reaction
Definition of the input function
NC: Normally closed
NO: Normally open
Disabled (0)
Fault (NC) Motor in On/Off (1)
Fault (NO) Motor in On/Off (2)
Fault (NC) Motor in On (3)
Fault (NO) Motor in On (4)
Warning (NC) Motor in On/Off (5)
Warning (NO) Motor in On/Off (6)
Warning (NC) Motor in On (7)
Warning (NO) Motor in On (8)
All
63/64
65/66
67/68
69/70
71/72
73/74
Aux Inp 1-6 message
Line 1/Line 2
Message text line 1 and line 2
Free text with 8 characters for
each line. Default: „Aux DIx“ with
x=1...6
DTM, UMC100-PAN
75 - 80
Aux Inp 1-6 delay
Input delay time in multiples of 100ms
0 ... 255 in multiples of 0.1s
Example: A value of 5 means
500ms
All excluding GSD-
PDQ22
137
PA R A M E T ER S A N D DATA S T R U C T U R E S O N A FI EL D B US
Содержание UMC100.3
Страница 1: ... MANUAL Univeral Motor Controller UMC100 3 ...