![ABB UMC100.3 Скачать руководство пользователя страница 153](http://html.mh-extra.com/html/abb/umc100-3/umc100-3_manual_2876153.webp)
AI111.0
General
Mounting
On DIN rail (EN 50022-35)
Mounting position
Any
Dimensions (W x H x D)
See Dimensions of expansion modules
LEDs: Red/yellow/green
Red: Hardware error of module
Yellow: Diagnosis available
Green: Ready for operation
Supply voltage
24 V DC (+30 % ... -20 %)
(19.2 ... 31.2 V DC) including ripple
Supply current
Max. 40 mA (at 19.2 ... 31.2 V DC)
Tightening torque for the communication terminals
see section DX1xx
Tightening torque for the input, output and supply terminals
see section DX1xx
Net weight
0.118 kg (0.260 lb)
Degree of protection
IP20
Temperature range
storage -25 ... +70 °C
operation 0 ... +60 °C
Marks, Approvals
CE, cUL
Further in preparation. Ask your local sales representative for other marks/
approvals.
Functional isolation between anlog inputs and 24 V DC supply /
communication interface
yes
Indiviual configuration of each analog input
yes
U
imp
sensor analog inputs
0.5 kV
Pollution degree terminals
3
Operation altitude above sea level
Up to 5000 m
Temperature Inputs
Type of connection
2 or 3 wire
Number of input channels
3 (one AI111.0) / 6 (two AI111.0)
Type of temperature inputs (adjustable per channel)
PT100 -50 °C...+400 °C
PT100 -50 °C...+70 °C
PT1000 -50 °C...+400°C
KTY83-110 -50 °C...+175 °C
KTY84-130 -40 °C...+300 °C
NTC +80…+160 °C [B75227-K333-A1]
Accuracy at 20 °C (T20)
m
± 2 K
Temperature coefficient
0.1K per K deviation from T20
Out of range detection
yes
Max. cable length
max. cable resistance: 50R (single wire)
[e.g. with copper wire 1.5mm²: 1900m cable length]
Cable shielding
Recommended for up to 30 m and outside the switchgear cabinet; shielding
mandatory for cables over 30 m
Update rate
typ. 600 ms
Sensor current (typ.)
PT100 1 mA
PT1000/KTY83/KTY84/NTC 0.2 mA
153
T EC H N I C A L DATA
Содержание UMC100.3
Страница 1: ... MANUAL Univeral Motor Controller UMC100 3 ...
Страница 159: ...159 ...