L1, L2, L3
3
24VDC/0V
K
k1
DOC DO0
DO1
DO2
UMC100
On
Off-N
COM
230VAC
1
2
3
*)
Connecting Contactors
—
Actual ABB contactors - all currents for 230 V AC (Extract):
Contactor type
Inrush current [A]
Holding current [A]
Inrush power [VA]
Holding power [VA]
B6S-30-10-2.8
1)
0.01
0.01
2.4
2.4
AF09Z - AF38Z
0.07
0.007
16
1.7
AF40 - AF65
0.11
0.017
25
4
AF80 - AF96
0.17
0.017
40
4
AF116 - AF146
0,56
0.026
130
6
AF190, AF205
0,96
0.03
220
7
AF265 - AF370
1.67
0.08
385
17.5
AF400, AF460, AF580, AF750
4.15
0.05
955
12
1)
The contactor B6S-30-10-2.8 (24 V DC) is recommended as interface contactor due to its internal spark suppression.
Spark suppression is necessary for all types except the AF types to maintain a reasonable service life.
—
Connection of contactors with electronic interface (AF types)
to the UMC100.3
*) Slide switch on the left side to position 'PLC' (up)
Connecting more than one expansion module
To connect several expansion modules to the UMC100.3 use the UMCIO-CAB cable to connect the first module with the UMC. And
use the IOIO-CAB cable to connect the first module with the second module and so on. The module order does not matter.
22
U MC10 0. 3 U N IVE R SA L MOTOR CONTROLLE R
T EC H N I C A L D E S C R I P T I O N