Digital Inputs
Isolation
No
Input signal bounce suppression
Typ. 2 ms
Signal 0 range including ripple
-31.2 ... +5 V
Signal 1 range including ripple
+15 ... +31.2 V
Input current per channel (24 V DC)
Typ. 6.0 mA
Input resistor to 0 V
3.9 k
Ω
Cable length
unshielded max. 600 m
shielded max. 1000 m
Relay Outputs
Number of relay outputs
3 x monostable with one common root
Voltage range of contacts
12 - 250 V AC/DC
Lowest switched power for correct signals
1 W or 1 VA
Switching capacity per relay contact acc. to EN 60947-5-1
(electromagnetic load)
AC-15 240 V AC: max. 1.5 A
AC-15 120 V AC: max. 3 A
DC-13 250 V DC max. 0.11 A
DC-13 125 V DC max. 0.22 A
DC-13 24 V DC max. 1 A
Short-circuit protection
6 A gG
U
imp
4 kV
Switching of inductive power
Inductive loads need additional measures for spark suppression. Diodes for DC
voltage and varistors / RC elements for AC voltage are suitable. Some DC coil
contactors contain rectifiers which suppress sparks perfectly.
Relay contact service life
Mechanical 500 000 switching cycles
Electrical (250 V AC):
0.5 A: 100 000 cycles
1.5 A 50 000 cycles
Internal clearance and creepage distances relay contacts to 24 V circuits
> 5.5 mm (safety insulation up to 250 V AC)
(EN 60947-1, Pollution degree 2)
Pollution degree terminals
3
Supply power down/up, behaviour: Valid for all motor control functions,
except transparent and overload relay.
Whenever the supply voltage of the UMC is switched off and on, the starting of
the motor needs a new RUN signal.
Digital Output
1SAJ530000R0***
1SAJ530000R1***
Max. output current
250 mA
250 mA
Short circuit protected
Yes
Yes
Output voltage if high
UMC100 supply voltage, nominal 24 V
DC
nominal 24V DC
Isolation
No
Yes, to AC mains
Thermistor Motor Protection (PTC - binary) Type A
Broken wire resistance
Voltage at broken wires between terminals T1/T2
> 4.8 k Ω
12 V DC (typ.)
Response resistance
3.4 - 3.8 k
Ω
Reset resistance
1.5 - 1.65 k
Ω
Short circuit resistance
Current at short circuit conditions
< 21
Ω
1.5 mA (typ.)
Response time
800 ms
Max. cold resistance of PTC sensor chain
< 1.5 k
Ω
Line length
2.5 mm
2
: 2 x 250 m
1.5 mm
2
: 2 x 150 m
0.5 mm
2
: 2 x 50 m
147
T EC H N I C A L DATA