Class 40E
Class 30E
Class 20E
Class 10E
Class 5E
Example of trip class selection:
Select the trip class so that the motor is thermally protected, even when the rotor is stalled. This means that the tripping curve of a
cold motor has to be below the coordination point Ia/Ie and tE whereas Ia is the actual current, Ie is the nominal current of the mo-
tor and tE is the maximal heating time as defined by the motor manufacturer. Example: Motor with enhanced safety has the data:
• Power = 7.5 kW
• Relation I
a
/I
e
= 7.4
• Heating time t
E
= 11 s
The following diagram shows the tripping time for cold motors at symmetric load:
The trip classes 5 and 10 are allowed because the appropriate times (3 s, 7 s) are below the time tE of the motor
(including the tolerance 10% of the UMC).
I
a
/I
e
=7,4
t
E
=11s
—
Example for the trip class selection for a given motor
39
CO N FI G U R I N G T H E M OTO R P R OT EC T I O N FU N C T I O N S