Pause
1start left
No start pos.
Starts left
Motor start cmd
3*
2
1
More than 1
start left
0
...
...
1
1
2
3
4
5
Pause
1 start left
No start pos.
Starts left
Motor start cmd
More than 1
start left
3*
2
1
0
...
...
1
1
2
3
4
5
1
16:00
16:10
t
t
Num Starts Window
Motor stopped
Motor stopped
15:00
14:00
Relevant Parameters:
• Num Starts Allowed
• Num Starts Window
• Num Starts Pause
• Num Starts Overrun
• Num Starts Prewarn
*) Initial counter setting depends on the parameter "
Num Starts Allowed
"
Example with 'Num Starts Allowed set to 3' shown at two points in time.
Once at 16.00 o'clock and then 10 min. later.
Top:
The 1st and 2nd start were successful. The 3rd start command was given before the pause time was over and was ignored
therefore. Then the 5th start was ignored too because only 3 starts are allowed in the time window.
Bottom:
The same situation is shown 10 min. later. One start is possible again because the first start was already shifted out of the
monitoring window.
—
Parameter combinations:
Num Starts Allowed
Num Starts Window
Num Starts Pause
Resulting Behaviour
0
0
0
Function not active.
(Default)
0
> 0
x
> 0
0
x
0
0
> 0
Number of starts not limited
but pause between starts active
> 0
> 0
0 or > 0
Number of starts limited, window
active (and pause active)
66
U MC10 0. 3 U N IVE R SA L MOTOR CONTROLLE R
T EC H N I C A L D E S C R I P T I O N