OPENCT
: Open CT detected
•
OPENCTAL
: Alarm issued after the setting delay
Outputs (positive integer) for information on the local HMI:
•
OPENCTIN
: Open CT in CT group inputs (1 for input 1 and 2 for input 2)
•
OPENCTPH
: Open CT with phase information (1 for phase L1, 2 for phase L2, 3 for phase L3)
6.3.3
Setting guidelines
SEMOD54832-1 v2
M12541-86 v4
Line differential protection receives information about currents from all line terminals and
evaluates this information in three different analysis blocks. The results of these analyses are
then forwarded to an output logic, where the conditions for trip or no trip are checked.
The three current analyses are:
•
Percentage restrained differential analysis
•
The 2
nd
and 5
th
harmonic analysis (only if there is a power transformer included in the
protected circuit)
•
Internal/external fault discriminator
6.3.3.1
General settings
M12541-93 v2
IBase set in primary Amp
M12541-95 v3
Set a common
IBase in Global base for the protected line (circuit). Most current settings for
the protection function are then related to the
IBase. The setting of IBase is normally made so
that it corresponds to the maximum rated CT in any of the line terminals. For example, if all
CTs used in a protected circuit are 1000A/1A, that is, the primary current rating is 1000 A, then
IBase = 1000 A is a good choice.
NoOfUsedCTs
M12541-98 v6
NoOfUsedCTs indicates to the function the number of three-phase CT sets included in the
protected circuit. Note that one IED can process one or two local current terminals of the
protected circuit. This is the case, for example, in 1½ breaker configurations in the line bay,
where each of the two CT sets will be represented as one separate current terminal. A
protected line with 1½ breaker configurations at each line end must consequently have
NoOfUsedCTs = 4.
NoOfUsedCTs indicates to the function the number of three-phase CT sets included in the
protected circuit. Note that one IED can process one or two local current terminals of the
protected circuit. This is the case, for example, in 1½ breaker configurations in the line bay,
where one of the two CT sets will be represented as one separate current terminal. A two-
terminal line with 1½ breaker configurations at one line end must consequently have
NoOfUsedCTs = 3.
IEC09000973-2-en.vsd
IEC09000973 V2 EN-US
Figure 54: Example when setting NoOfUsedCTs = 4 in 1½ breaker configurations
1MRK 505 343-UEN B
Section 6
Differential protection
123
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...