set using the
tPulse parameter. Also, being accessible on the single line diagram (SLD), this
function block has two control modes (settable through
CtlModel): Dir Norm and SBO Enh.
14.7
Generic communication function for Double Point
indication DPGAPC
SEMOD55384-1 v4
14.7.1
Identification
GUID-E16EA78F-6DF9-4B37-A92D-5C09827E2297 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Generic communication function for
Double Point indication
DPGAPC
-
-
14.7.2
Application
SEMOD55391-5 v8
Generic communication function for Double Point indication (DPGAPC) function block is used
to send double point position indication to other systems, equipment or functions in the
substation through IEC 61850-8-1 or other communication protocols. It is especially intended
to be used in the interlocking station-wide logics. To be able to get the signals into other
systems, equipment or functions, one must use other tools, described in the Engineering
manual, and define which function block in which systems, equipment or functions should
receive this information.
More specifically, DPGAPC function reports a combined double point position indication
output POSITION, by evaluating the value and the timestamp attributes of the inputs OPEN
and CLOSE, together with the logical input signal VALID.
When the input signal VALID is active, the values of the OPEN and CLOSE inputs determine the
two-bit integer value of the output POSITION. The timestamp of the output POSITION will have
the latest updated timestamp of the inputs OPEN and CLOSE.
When the input signal VALID is inactive, DPGAPC function forces the position to intermediated
state.
When the value of the input signal VALID changes, the timestamp of the output POSITION will
be updated as the time when DPGAPC function detects the change.
Refer to Table
for the description of the input-output relationship in terms of the value and
the quality attributes.
Table 49: Description of the input-output relationship
VALID
OPEN
CLOSE
POSITION
Value
Description
0
-
-
0
Intermediate
1
0
0
0
Intermediate
1
1
0
1
Open
1
0
1
2
Closed
1
1
1
3
Bad State
1MRK 505 343-UEN B
Section 14
Control
593
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...