UGenZeroDb: Minimum level of voltage in % of UBase used as indication of zero voltage (zero
point clamping). If measured value is below
UGenZeroDb calculated S, P, Q and PF will be zero.
IGenZeroDb: Minimum level of current in % of IBase used as indication of zero current (zero
point clamping). If measured value is below
IGenZeroDb calculated S, P, Q and PF will be zero.
UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y% of Ur, where
Y is equal to 5, 30 or 100.
IAmpCompY: Amplitude compensation to calibrate current measurements at Y% of Ir, where Y
is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir, where Y is
equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase current measurement
(CMMXU).
IAmpCompY: Amplitude compensation to calibrate current measurements at Y% of Ir, where Y
is equal to 5, 30 or 100.
IAngCompY: Angle compensation to calibrate angle measurements at Y% of Ir, where Y is
equal to 5, 30 or 100.
The following general settings can be set for the Phase-phase voltage measurement
(VMMXU).
UAmpCompY: Amplitude compensation to calibrate voltage measurements at Y% of Ur, where
Y is equal to 5, 30 or 100.
UAngCompY: Angle compensation to calibrate angle measurements at Y% of Ur, where Y is
equal to 5, 30 or 100.
The following general settings can be set for all monitored quantities included in the
functions (CVMMXN, CMMXU, VMMXU, CMSQI, VMSQI, VNMMXU) X in setting names below
equals S, P, Q, PF, U, I, F, IL1-3, UL1-3UL12-31, I1, I2, 3I0, U1, U2 or 3U0.
Xmin: Minimum value for analog signal X set directly in applicable measuring unit.
Xmax: Maximum value for analog signal X.
XZeroDb: Zero point clamping. A signal value less than XZeroDb is forced to zero.
Observe the related zero point clamping settings in Setting group N for CVMMXN
(
UGenZeroDb and IGenZeroDb). If measured value is below UGenZeroDb and/or IGenZeroDb
calculated S, P, Q and PF will be zero and these settings will override
XZeroDb.
XRepTyp: Reporting type. Cyclic (Cyclic), amplitude deadband (Dead band) or integral
deadband (
Int deadband). The reporting interval is controlled by the parameter XDbRepInt.
XDbRepInt: Reporting deadband setting. Cyclic reporting is the setting value and is reporting
interval in seconds. Amplitude deadband is the setting value in % of measuring range. Integral
deadband setting is the integral area, that is, measured value in % of measuring range
multiplied by the time between two measured values.
XHiHiLim: High-high limit. Set in applicable measuring unit.
XHiLim: High limit.
XLowLim: Low limit.
XLowLowLim: Low-low limit.
Section 17
1MRK 505 343-UEN B
Monitoring
654
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...