14.4.9.1
Application
M13570-3 v6
The interlocking for 1 1/2 breaker diameter (BH_CONN, BH_LINE_A, BH_LINE_B) functions are
used for lines connected to a 1 1/2 breaker diameter according to figure
.
WA1 (A)
WA2 (B)
QB1
QC1
QA1
QC2
QC9
QB6
QB9
QB2
QC1
QA1
QC2
QC3
QB6
QC3
QB62
QB61
QA1
QC1
QC2
QC9
QB9
BH_LINE_A
BH_LINE_B
BH_CONN
en04000513.vsd
IEC04000513 V1 EN-US
Figure 369: Switchyard layout 1 1/2 breaker
M13570-7 v4
Three types of interlocking modules per diameter are defined. BH_LINE_A and BH_LINE_B are
the connections from a line to a busbar. BH_CONN is the connection between the two lines of
the diameter in the 1 1/2 breaker switchyard layout.
M13569-4 v4
For a 1 1/2 breaker arrangement, the modules BH_LINE_A, BH_CONN and BH_LINE_B must be
used.
14.4.9.2
Configuration setting
M13569-6 v5
For application without QB9 and QC9, just set the appropriate inputs to open state and
disregard the outputs. In the functional block diagram, 0 and 1 are designated 0=FALSE and
1=TRUE:
•
QB9_OP = 1
•
QB9_CL = 0
•
QC9_OP = 1
•
QC9_CL = 0
If, in this case, line voltage supervision is added, then rather than setting QB9 to open state,
specify the state of the voltage supervision:
•
QB9_OP = VOLT_OFF
•
QB9_CL = VOLT_ON
Section 14
1MRK 505 343-UEN B
Control
590
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...