10.2.3
Setting guidelines
M14959-3 v7
All the frequency and voltage magnitude conditions in the system where SAPTOF performs its
functions must be considered. The same also applies to the associated equipment, its
frequency and time characteristic.
There are two application areas for SAPTOF:
1.
to protect equipment against damage due to high frequency, such as generators, and
motors
2.
to protect a power system, or a part of a power system, against breakdown, by shedding
generation, in over production situations.
The overfrequency start value is set in Hz. All voltage magnitude related settings are made as a
percentage of a settable global base voltage parameter
UBase. The UBase value should be set
as a primary phase-to-phase value.
Some applications and related setting guidelines for the frequency level are given below:
Equipment protection, such as for motors and generators
The setting has to be well above the highest occurring "normal" frequency and well below the
highest acceptable frequency for the equipment.
Power system protection, by generator shedding
The setting must be above the highest occurring "normal" frequency and below the highest
acceptable frequency for power stations, or sensitive loads. The setting level, the number of
levels and the distance between two levels (in time and/or in frequency) depend very much on
the characteristics of the power system under consideration. The size of the "largest loss of
load" compared to "the size of the power system" is a critical parameter. In large systems, the
generator shedding can be set at a fairly low frequency level, and the time delay is normally not
critical. In smaller systems the frequency START level has to be set at a higher value, and the
time delay must be rather short.
10.3
Rate-of-change frequency protection SAPFRC
IP15748-1 v3
10.3.1
Identification
M14868-1 v3
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Rate-of-change frequency protection
SAPFRC
df/dt
><
SYMBOL-N V1 EN-US
81
10.3.2
Application
M14966-3 v4
Rate-of-change frequency protection (SAPFRC), is applicable in all situations, where reliable
detection of change of the fundamental power system voltage frequency is needed. SAPFRC
can be used both for increasing frequency and for decreasing frequency. SAPFRC provides an
output signal, suitable for load shedding or generator shedding, generator boosting, HVDC-
set-point change, gas turbine start up and so on. Very often SAPFRC is used in combination
1MRK 505 343-UEN B
Section 10
Frequency protection
491
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...