RFPP 1.6 Zload
£
×
load
1.6 Z
£
×
RFPP
EQUATION579 V2 EN-US
(Equation 289)
Equation
is applicable only when the loop characteristic angle for the phase-to-phase
faults is more than three times as large as the maximum expected load-impedance angle. More
accurate calculations are necessary according to equation
.
load min
R1
RFPP 1.6 Z
cos
sin
X1
J
J
£
×
-
×
é
ù
× ê
ú
ë
û
IECEQUATION2307 V1 EN-US
(Equation 290)
All this is applicable for all measuring zones when no Power swing detection function ZMRPSB
is activated in the IED. Use an additional safety margin of approximately 20% in cases when a
ZMRPSB function is activated in the IED, refer to the description of Power swing detection
function ZMRPSB.
7.9.3.8
Load impedance limitation, with Phase selection with load
encroachment, quadrilateral characteristic function activated
GUID-68C89E77-77E1-47A2-A0D2-B6236CB63AB1 v1
The parameters for shaping of the load encroachment characteristic are found in the
description of Phase selection with load encroachment, quadrilateral characteristic function
(FRPSPDIS).
7.9.3.9
Setting of minimum operating currents
GUID-DAFBA182-ABD1-42F7-B958-E292B8E0E161 v1
The operation of Distance protection zone, quadrilateral characteristic (ZMQPDIS) can be
blocked if the magnitude of the currents is below the set value of the parameter
IMinOpPP and
IMinOpPE.
The default setting of
IMinOpPP and IMinOpPE is 20% of IBase where IBase is the chosen
current for the analogue input channels. The value has been proven in practice to be suitable in
most of the applications. However, there might be applications where it is necessary to
increase the sensitivity by reducing the minimum operating current down to 10% of
IBase. This
happens especially in cases, when the IED serves as a remote back-up protection on series of
very long transmission lines.
Setting
IMinOpIN blocks the phase-to-earth loop if 3I
0
<
IMinOpIN. The default setting of
IMinOpIN is 5% of IBase.
The minimum operating fault current is automatically reduced to 75% of its set value, if the
distance protection zone has been set for the operation in reverse direction.
7.9.3.10
Setting of timers for distance protection zones
GUID-E6DD460D-2189-45E9-AD4D-E127DCA8EBAC v1
The required time delays for different distance protection zones are independent of each
other. Distance protection zone 1 can also have a time delay, if so required for selectivity
reasons. Time delays for all zones can be set in a range of 0 to 60 seconds. The tripping
function of each particular zone can be inhibited by setting the corresponding
Operation
parameter to
Off. Different time delays are possible for the phase-to-earthtPE and for the
Section 7
1MRK 505 343-UEN B
Impedance protection
284
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...