phase fault for φline>70° (setting parameters in italic)
7.10.4
Setting guidelines
IP14959-1 v2
The following setting guideline consider normal overhead lines applications where φloop and
φline is greater than 60°.
7.10.4.1
Resistive reach with load encroachment characteristic
M13142-312 v4
The procedure for calculating the settings for the load encroachment consist basically to
define the load angle
ArgLd, the blinder RLdFw in forward direction and blinder RLdRv in
reverse direction, as shown in figure