IEC13000016-2-en.vsd
IEC13000016 V2 EN-US
Figure 326: APC - Local remote function block
14.3.1.2
Switch controller (SCSWI)
M16596-3 v4
SCSWI may handle and operate on one three-phase device or three one-phase switching
devices.
After the selection of an apparatus and before the execution, the switch controller performs
the following checks and actions:
•
A request initiates to reserve other bays to prevent simultaneous operation.
•
Actual position inputs for interlocking information are read and evaluated if the operation
is permitted.
•
The synchrocheck/synchronizing conditions are read and checked, and performs
operation upon positive response.
•
The blocking conditions are evaluated
•
The position indications are evaluated according to given command and its requested
direction (open or closed).
The command sequence is supervised regarding the time between:
•
Select and execute.
•
Select and until the reservation is granted.
•
Execute and the final end position of the apparatus.
•
Execute and valid close conditions from the synchrocheck.
At error the command sequence is cancelled.
Section 14
1MRK 505 343-UEN B
Control
554
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...