Earth fault indications in monitor direction
Function block with defined functions for earth fault indications in monitor direction, I103EF.
This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER
parameter is defined for each output signal.
•
Fault indications in monitor direction
Function block with defined functions for fault indications in monitor direction, I103FLTPROT.
This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER
parameter is defined for each input signal.
This block is suitable for distance protection, line differential, transformer differential, over-
current and earth-fault protection functions.
•
Autorecloser indications in monitor direction
Function block with defined functions for autorecloser indications in monitor direction,
I103AR. This block includes the FUNCTION TYPE parameter, and the INFORMATION NUMBER
parameter is defined for each output signal.
Measurands
M17109-99 v2
The measurands can be included as type 3.1, 3.2, 3.3, 3.4 and type 9 according to the standard.
•
Measurands in public range
Function block that reports all valid measuring types depending on connected signals,
I103Meas.
•
Measurands in private range
Function blocks with user defined input measurands in monitor direction, I103MeasUsr. These
function blocks include the FUNCTION TYPE parameter for each block in the private range, and
the INFORMATION NUMBER parameter for each block.
Fault location
M17109-108 v1
The fault location is expressed in reactive ohms. In relation to the line length in reactive ohms,
it gives the distance to the fault in percent. The data is available and reported when the fault
locator function is included in the IED.
Disturbance recordings
M17109-111 v8
•
The transfer functionality is based on the Disturbance recorder function. The analog and
binary signals recorded will be reported to the master by polling. The eight last
disturbances that are recorded are available for transfer to the master. A file that has
been transferred and acknowledged by the master cannot be transferred again.
•
The binary signals that are included in the disturbance recorder are those that are
connected to the disturbance function blocks B1RBDR to B6RBDR. These function blocks
include the function type and the information number for each signal. For more
information on the description of the Disturbance report in the Technical reference
manual. The analog channels, that are reported, are those connected to the disturbance
function blocks A1RADR to A4RADR. The eight first ones belong to the public range and
the remaining ones to the private range.
Settings
M17109-116 v1
Section 19
1MRK 505 343-UEN B
Station communication
702
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...