Substation A
Substation B
Z
lineAB,1
(pos. seq)
Z
lineAB,0
(zero seq)
Z
lineBC,1
(pos. seq)
Z
lineBC,0
(zero seq)
U
0A
U
0B
3I
0
Phase to earth fault
R
N
Z
T,1
(pos. seq)
Z
T,0
(zero seq)
Source impedance
Z
sc
(pos. seq)
en06000654.vsd
IEC06000654 V1 EN-US
Figure 286: Equivalent of power system for calculation of setting
The residual fault current can be written:
phase
0
1
0
f
3U
3I
2 Z
Z
3 R
=
×
+
+ ×
EQUATION1948 V1 EN-US
(Equation 496)
Where
U
phase
is the phase voltage in the fault point before the fault
Z
1
is the total positive sequence impedance to the fault point. Z
1
= Z
sc
+Z
T,1
+Z
lineAB,1
+Z
lineBC,1
Z
0
is the total zero sequence impedance to the fault point. Z
0
= Z
T,0
+3R
N
+Z
lineAB,0
+Z
lineBC,0
R
f
is the fault resistance.
The residual voltages in stations A and B can be written:
(
)
0 A
0
T ,0
N
U
3I
Z
3R
=
×
+
EQUATION1949 V1 EN-US
(Equation 497)
OB
0
T ,0
N
lineAB,0
U
3I (Z
3R
Z
)
=
×
+
+
EQUATION1950 V1 EN-US
(Equation 498)
The residual power, measured by the sensitive earth fault protections in A and B will be:
1MRK 505 343-UEN B
Section 8
Current protection
437
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...