The residual power is a complex quantity. The protection will have a maximum sensitivity in
the characteristic angle RCA. The apparent residual power component in the characteristic
angle, measured by the protection, can be written:
0 A ,prot
0 A
0
A
S
3U
3I cos
j
=
×
×
EQUATION1953 V1 EN-US
(Equation 501)
0 B,prot
0 B
0
B
S
3U
3I cos
j
=
×
×
EQUATION1954 V1 EN-US
(Equation 502)
The angles φ
A
and φ
B
are the phase angles between the residual current and the residual
voltage in the station compensated with the characteristic angle RCA.
The protection will use the power components in the characteristic angle direction for
measurement, and as base for the inverse time delay.
The inverse time delay is defined as:
0
0
inv
0
0
kSN (3I 3U cos (reference))
t
3I 3U cos (measured)
×
×
×
j
=
×
×
j
EQUATION1942 V2 EN-US
(Equation 503)
The function can be set
On/Off with the setting of Operation.
Common base IED values for primary current (IBase), primary voltage (UBase) and primary
power (SBase) are set in a Global base values for settings function GBASVAL.
GlobalBaseSel: It is used to select a GBASVAL function for reference of base values.
RotResU: It is a setting for rotating the polarizing quantity ( 3U
0
) by 0 or 180 degrees. This
parameter is set to 180 degrees by default in order to inverse the residual voltage ( 3U
0
) to
calculate the reference voltage (-3U
0
e
-jRCADir
). Since the reference voltage is used as the
polarizing quantity for directionality, it is important to set this parameter correctly.
With the setting
OpMode the principle of directional function is chosen.
With
OpMode set to 3I0cosfi the current component in the direction equal to the characteristic
angle
RCADir has the maximum sensitivity. The characteristic for RCADir is equal to 0° is shown
Section 8
1MRK 505 343-UEN B
Current protection
438
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...