Figure 271: Through fault current from B to A: I
fA
The function shall not operate for any of the calculated currents to the protection. The
minimum theoretical current setting (Imin) will be:
Imin MAX I
fA
I
fA
,
(
)
³
EQUATION284 V1 EN-US
(Equation 479)
A safety margin of 5% for the maximum static inaccuracy and a safety margin of 5% for
maximum possible transient overreach have to be introduced. An additional 20% is suggested
due to inaccuracy of instrument transformers under transient conditions and inaccuracy in the
system data.
The minimum primary current setting (Is) is:
I
s
= 1.3 ×
I
min
EQUATION285 V3 EN-US
(Equation 480)
In case of parallel lines with zero sequence mutual coupling a fault on the parallel line, as
shown in figure
, should be calculated.
IEC09000025-1-en.vsd
~
~
Z
A
Z
B
Z
L1
A
B
I
M
Fault
IED
Z
L2
M
C
Line 1
Line 2
IEC09000025 V1 EN-US
Figure 272: Two parallel lines. Influence from parallel line to the through fault current: I
M
The minimum theoretical current setting (Imin) will in this case be:
Section 8
1MRK 505 343-UEN B
Current protection
416
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...