7.9.3.6
Setting of reach in resistive direction
GUID-3BFE80FD-8A51-4B71-8762-73DFA73AB28B v2
Set the resistive independently for each zone.
Set separately the expected fault resistance for phase-to-phase faults
RFPP and for the phase-
to-earth faults
RFPE for each zone. For each distance zone, set all remaining reach setting
parameters independently of each other.
The final reach in resistive direction for phase-to-earth fault loop measurement automatically
follows the values of the line-positive and zero-sequence resistance, and at the end of the
protected zone is equal to equation
.
(
)
1
R
2 R1 R0
RFPE
3
=
×
+
+
IECEQUATION2303 V1 EN-US
(Equation 281)
2 X1 X0
arctan
2 R1 R0
loop
j
×
+
=
×
+
é
ù
ê
ú
ë
û
EQUATION2304 V1 EN-US
(Equation 282)
Setting of the resistive reach for the underreaching zone 1 should follow the condition to
minimize the risk for overreaching:
RFPE
4.5 X1
£
×
IECEQUATION2305 V1 EN-US
(Equation 283)
The fault resistance for phase-to-phase faults is normally quite low, compared to the fault
resistance for phase-to-earth faults. To minimize the risk for overreaching, limit the setting of
the zone1 reach in resistive direction for phase-to-phase loop measurement in the phase
domain to:
RFPP
X
≤ ⋅
6
1
IECEQUATION2306 V2 EN-US
(Equation 284)
7.9.3.7
Load impedance limitation, without load encroachment function
GUID-A7CDE76A-D5B5-4641-9324-2E9A99071DF5 v1
The following instructions are valid when Phase selection with load enchroachment,
quadrilateral characteristic function FRPSPDIS is not activated. To deactivate the function, the
setting of the load resistance
RLdFw and RLdRv in FRPSPDIS must be set to max value (3000).
If FRPSPDIS is to be used for all or some of the measuring zones, the load limitation for those
zones according to this chapter can be omitted. Check the maximum permissible resistive
Section 7
1MRK 505 343-UEN B
Impedance protection
282
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...