If IEC 61850-9-2LE communication is interrupt, data from the merging units
(MU) after the time for interruption will be incorrect. Both data stored in the
IED and displayed on the local HMI will be corrupt. For this reason it is
important to connect signal from respective MU units (SMPLLOST) to the
disturbance recorder.
Forcing of binary inputs and outputs is a convenient way to test wiring in substations as well
as testing configuration logic in the IEDs. Basically it means that all binary inputs and outputs
on the IED I/O modules (BOM, BIM, IOM & SOM) can be forced to arbitrary values.
Central Account Management is an authentication infrastructure that offers a secure solution
for enforcing access control to IEDs and other systems within a substation. This incorporates
management of user accounts, roles and certificates and the distribution of such, a procedure
completely transparent to the user.
Flexible Product Naming allows the customer to use an IED-vendor independent 61850 model
of the IED. This customer model will be used as the IEC 61850 data model, but all other aspects
of the IED will remain unchanged (e.g., names on the local HMI and names in the tools). This
offers significant flexibility to adapt the IED to the customers system and standard solution
The logic is prepared with a graphical tool. The advanced logic capability allows special
applications such as automatic opening of disconnectors in multi-breaker arrangements,
closing of breaker rings, load transfer logics etc. The graphical configuration tool ensures
simple and fast testing and commissioning.
A loop testing function allows complete testing including remote end IED when local IED is set
in test mode.
M11788-3 v10
Communication via optical connections ensures immunity against disturbances.
2.2
Main protection functions
GUID-66BAAD98-851D-4AAC-B386-B38B57718BD2 v12.1.1
Table 2:
Example of quantities
2
= number of basic instances
0-3
= option quantities
3-A03
= optional function included in packages A03 (refer to ordering details)
IEC 61850
ANSI
Function description
Line Differential
RED670
(Customized)
RED670 (A31)
RED670 (B31)
RED670 (A32)
RED670 (B32)
Differential protection
HZPDIF
87
1Ph high impedance
differential protection
0-3
3-A02
3-A02
3-A02
3-A02
REFPDIF
87N
Restricted earth fault
protection, low impedance
0–2
L3CPDIF
87L
Line differential protection,
3 CT sets, 2–3 line ends
1
1
1
L6CPDIF
87L
Line differential protection,
6 CT sets, 3–5 line ends
1
1-A04
1
1-A04
1
LT3CPDIF
87LT
Line differential protection,
3 CT sets, with inzone
transformers, 2–3 line ends
1
1-A05
1-A05
Table continues on next page
Section 2
1MRK 505 343-UEN B
Application
36
Application manual
Содержание Relion 670 series
Страница 1: ...RELION 670 SERIES Line differential protection RED670 Version 2 1 IEC Application manual...
Страница 2: ......
Страница 40: ...34...
Страница 64: ...58...
Страница 150: ...144...
Страница 406: ...400...
Страница 472: ...466...
Страница 494: ...488...
Страница 512: ...506...
Страница 524: ...518...
Страница 604: ...598...
Страница 686: ...680...
Страница 718: ...712...
Страница 722: ...716...
Страница 758: ...752...
Страница 759: ...753...