13.1.4
Signals
Table 201:
CCSSPVC (87) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for three phase current input
IREF
GROUP
SIGNAL
-
Residual reference current input
BLOCK
BOOLEAN
0
Block of function
Table 202:
CCSSPVC (87) Output signals
Name
Type
Description
FAIL
BOOLEAN
Detection of current circuit failure
ALARM
BOOLEAN
Alarm for current circuit failure
13.1.5
Settings
Table 203:
CCSSPVC (87) Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
IMinOp
10 - 200
%IB
1
20
Minimum operate current differential pickup in
% of IBase
Table 204:
CCSSPVC (87) Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
Pickup_Block
20 - 500
%IB
1
150
Block of the function at high phase current, in %
of IBase
Table 205:
CCSSPVC (87) Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
Section 13
1MRK 511 365-UUS A
Secondary system supervision
360
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...