When EnaAbs
is set as absolute comparison and
SetValue
is set less than
0.2% of the set unit then INLOW output will never pickups. During the
above mentioned condition, due to marginal value for avoiding
oscillations of function outputs, the INLOW output will never set.
15.16.7
Technical data
REALCOMP function can compare the values from milli value level to giga value level
and the maximum expectable accuracy level from the function is 10 µ.
Table 375:
REALCOMP Technical data
Function
Accuracy
Operate value,
EqualBandHigh
and EqualBandLow
±0.5% of set value
Reset value,
EqualBandHigh
> 0.1% of set RefPrefix
Reset value,
EqualBandLow
< 0.1% of set RefPrefix
Table 376:
Number of REALCOMP instances
Function
Quantity with cycle time
3 ms
8 ms
100 ms
REALCOMP
4
4
4
Section 15
1MRK 511 365-UUS A
Logic
482
Phasor measurement unit RES670 2.1 ANSI
Technical manual