Name
Type
Values (Range)
Unit
Description
BO21
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 21 status
BO22VALUE
BOOLEAN
1=1
0=0
-
Binary output 22 value
BO22FORCE
BOOLEAN
0=Normal
1=Forced
-
Binary output 22 force
BO22
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 22 status
BO23VALUE
BOOLEAN
1=1
0=0
-
Binary output 23 value
BO23FORCE
BOOLEAN
0=Normal
1=Forced
-
Binary output 23 force
BO23
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 23 status
BO24VALUE
BOOLEAN
1=1
0=0
-
Binary output 24 value
BO24FORCE
BOOLEAN
0=Normal
1=Forced
-
nary output 24 force
BO24
BOOLEAN
0=Normal
1=Forced
2=Blocked
-
Binary output 24 status
21.2.8.6
Technical data
Table 653:
BOM - Binary output module contact data (reference standard: IEC 61810-2)
Function or quantity
Trip and Signal relays
Binary outputs
24
Max system voltage
250 V AC, DC
Test voltage across open contact, 1 min
1000 V rms
Current carrying capacity
Per relay, continuous
Per relay, 1 s
Per process connector pin, continuous
8 A
10 A
12 A
Making capacity at inductive load with L/R>10 ms
0.2 s
1.0 s
30 A
10 A
Breaking capacity for AC, cos
j
>0.4
250 V/8.0 A
Breaking capacity for DC with L/R < 40 ms
48 V/1 A
110 V/0.4 A
125 V/0.35 A
220 V/0.2 A
250 V/0.15 A
1MRK 511 365-UUS A
Section 21
IED hardware
Phasor measurement unit RES670 2.1 ANSI
779
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...