10.4.4
Signals
Table 179:
FTAQFVR (81A) Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Group signal for three phase current
V3P
GROUP
SIGNAL
-
Group signal for three phase voltage
BLOCK
BOOLEAN
0
Block of function
CBCLOSE
BOOLEAN
0
Circuit breaker closed status input
CBOPEN
BOOLEAN
0
Circuit breaker open status input
LOADINIT
BOOLEAN
0
Loads the initial accumulation time to the function
HOLDACC
BOOLEAN
0
Holds the time accumulation when input is activated
RESETACC
BOOLEAN
0
Resetting the accumulated time of the function block
Table 180:
FTAQFVR (81A) Output signals
Name
Type
Description
ERROR
BOOLEAN
Error output for incorrect settings
TRIP
BOOLEAN
Trip signal of the function
TRIPACC
BOOLEAN
Trip signal when accumulation time is exceeded the set
limit
TRIPCONT
BOOLEAN
Trip signal when continuous time is exceeded the set
limit
BFI_3P
BOOLEAN
Pickup signal of the function
ACCALARM
BOOLEAN
Alarm signal for reaching the frequency time
accumulation value
STRORHLD
BOOLEAN
Activated when function starts or HOLDACC input is
active
FREQOK
BOOLEAN
Indicates the system frequency within the frequency
band limits
VOLTOK
BOOLEAN
Indicates the system voltage within the voltage band
limits
Section 10
1MRK 511 365-UUS A
Frequency protection
314
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...