Name
Values (Range)
Unit
Step
Default
Description
tCCrv2
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time curve
for step 2
tPRCrv2
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 2
tTRCrv2
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 2
tCRCrv2
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse reset time
curve for step 2
ResetTypeCrv3
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step3 (Instantaneous /
IEC / ANSI)
tReset3
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 3
tPCrv3
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time curve
for step 3
tACrv3
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time curve
for step 3
tBCrv3
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time curve
for step 3
tCCrv3
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time curve
for step 3
tPRCrv3
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 3
tTRCrv3
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 3
tCRCrv3
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset time
curve for step 3
ResetTypeCrv4
Instantaneous
IEC Reset
ANSI reset
-
-
Instantaneous
Reset curve type for step4 (Instantaneous /
IEC / ANSI)
tReset4
0.000 - 60.000
s
0.001
0.020
Reset time delay for step 4
tPCrv4
0.005 - 3.000
-
0.001
1.000
Param P for customized inverse trip time curve
for step 4
tACrv4
0.005 - 200.000
-
0.001
13.500
Param A for customized inverse trip time curve
for step 4
tBCrv4
0.00 - 20.00
-
0.01
0.00
Param B for customized inverse trip time curve
for step 4
tCCrv4
0.1 - 10.0
-
0.1
1.0
Param C for customized inverse trip time curve
for step 4
tPRCrv4
0.005 - 3.000
-
0.001
0.500
Param PR for customized inverse reset time
curve for step 4
tTRCrv4
0.005 - 100.000
-
0.001
13.500
Param TR for customized inverse reset time
curve for step 4
tCRCrv4
0.1 - 10.0
-
0.1
1.0
Param CR for customized inverse reset time
curve for step 4
1MRK 511 365-UUS A
Section 8
Current protection
Phasor measurement unit RES670 2.1 ANSI
219
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...