14.1.5
Settings
Table 215:
SLGAPC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
NrPos
2 - 32
-
1
32
Number of positions in the switch
OutType
Pulsed
Steady
-
-
Steady
Output type, steady or pulse
tPulse
0.000 - 60.000
s
0.001
0.200
Operate pulse duration, in [s]
tDelay
0.000 - 60000.000
s
0.010
0.000
Time delay on the output, in [s]
StopAtExtremes
Disabled
Enabled
-
-
Disabled
Stop when min or max position is reached
14.1.6
Monitored data
Table 216:
SLGAPC Monitored data
Name
Type
Values (Range)
Unit
Description
SWPOSN
INTEGER
-
-
Switch position (integer)
14.1.7
Operation principle
The logic rotating switch for function selection and LHMI presentation (SLGAPC)
function has two operating inputs – UP and DOWN. When a signal is received on the UP
input, the function will activate the output next to the present activated output, in
ascending order (for example if the present activated output is P03 and one activates the
UP input then the output P04 will be activated). When a signal is received on the DOWN
input, the function will activate the output next to the present activated output, in
descending order (for example if the present activated output is P03 and one activates the
DOWN input then the output P02 will be activated). Depending on the output settings the
output signals can be steady or pulsed. In case of steady signals, the output will be active
till the time it receives next operation of UP/DOWN inputs. Also, depending on the
settings one can have a time delay between the UP or DOWN activation signal positive
front and the output activation.
Besides the inputs visible in the application configuration in the Application
Configuration tool, there are other possibilities that will allow an user to set the desired
position directly (without activating the intermediate positions), either locally or
remotely, using a “select before execute” dialog. One can block the function operation, by
activating the BLOCK input. In this case, the present position will be kept and further
operation will be blocked. The operator place (local or remote) is specified through the
Section 14
1MRK 511 365-UUS A
Control
380
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...