14.2.5
Settings
Table 219:
VSGAPC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
CtlModel
Dir Norm
SBO Enh
-
-
Dir Norm
Specifies the type for control model according
to IEC 61850
Mode
Steady
Pulsed
-
-
Pulsed
Operation mode
tSelect
0.000 - 60.000
s
0.001
30.000
Max time between select and execute signals
tPulse
0.000 - 60.000
s
0.001
0.200
Command pulse lenght
14.2.6
Operation principle
Selector mini switch (VSGAPC) function can be used for double purpose, in the same way
as switch controller (SCSWI) functions are used:
•
for indication on the single line diagram (SLD). Position is received through the
IPOS1 and IPOS2 inputs and distributed in the configuration through the POS1 and
POS2 outputs, or to IEC 61850 through reporting, or GOOSE.
•
for commands that are received via the local HMI or IEC 61850 and distributed in the
configuration through outputs CMDPOS12 and CMDPOS21.
The output CMDPOS12 is set when the function receives a CLOSE command from
the local HMI when the SLD is displayed and the object is chosen.
The output CMDPOS21 is set when the function receives an OPEN command from
the local HMI when the SLD is displayed and the object is chosen.
It is important for indication in the SLD that the a symbol is associated
with a controllable object, otherwise the symbol won't be displayed on the
screen. A symbol is created and configured in GDE tool in PCM600.
The PSTO input is connected to the Local remote switch to have a selection of operators
place, operation from local HMI (Local) or through IEC 61850 (Remote). An INTONE
connection from Fixed signal function block (FXDSIGN) will allow operation from local
HMI.
As it can be seen, both indications and commands are done in double-bit representation,
where a combination of signals on both inputs/outputs generate the desired result.
The following table shows the relationship between IPOS1/IPOS2 inputs and the name of
the string that is shown on the SLD. The value of the strings are set in PST.
Section 14
1MRK 511 365-UUS A
Control
384
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...