_
_
ref A
A
dir A
A
V
V
I
I
=
=
ANSIEQUATION1452 V1 EN
(Equation 11)
_
_
ref B
B
dir B
B
V
V
I
I
=
=
ANSIEQUATION1453 V1 EN
(Equation 12)
_
_
ref C
C
dir C
C
V
V
I
I
=
=
ANSIEQUATION1454 V1 EN
(Equation 13)
The polarizing voltage is available as long as the positive-sequence voltage exceeds 4%
of the set base voltage
VBase
. So the directional element can use it for all unsymmetrical
faults including close-in faults.
For close-in three-phase faults, the V1
AM
memory voltage, based on the same positive
sequence voltage, ensures correct directional discrimination.
The memory voltage is used for 100 ms or until the positive sequence voltage is restored.
After 100 ms, the following occurs:
•
If the current is still above the set value of the minimum operating current (between
10 and 30% of the set terminal rated current
IBase
), the condition seals in.
•
If the fault has caused tripping, the trip endures.
•
If the fault was detected in the reverse direction, the measuring element in the
reverse direction remains in operation.
•
If the current decreases below the minimum operating value, the memory resets until
the positive sequence voltage exceeds 10% of its rated value.
The directional setting is given as a characteristic angle
AngleRCA
for the function and an
angle window
ROADir
.
Section 8
1MRK 511 365-UUS A
Current protection
182
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...