Command handling
•
Autorecloser ON/OFF
•
Teleprotection ON/OFF
•
Protection ON/OFF
•
LED reset
•
Characteristics 1 - 4 (Setting groups)
•
File transfer (disturbance files)
•
Time synchronization
For detailed information about IEC 60870-5-103, refer to the IEC 60870 standard part 5:
Transmission protocols, and to the section 103: Companion standard for the informative
interface of protection equipment.
IEC 60870-5-103 vendor specific implementation
The signal and setting tables specify the information types supported by the IEDs with the
communication protocol IEC 60870-5-103 implemented.
The information types are supported when corresponding functions are included in the
protection and control IED.
Be aware of that different cycle times for function blocks must be
considered to ensure correct time stamping.
Commands in control direction
Commands in control direction, I103IEDCMD
Command block in control direction with defined output signals.
Number of instances: 1
Function type is selected with parameter
FunctionType
.
Information number is defined for each output signals.
Table 537:
I103IEDCMD supported indications
INF
Description
19
LED Reset
23
Activate setting group 1
24
Activate setting group 2
25
Activate setting group 3
26
Activate setting group 4
Function commands in control direction, pre-defined I103CMD
Section 18
1MRK 511 365-UUS A
Station communication
662
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...