Name
Values (Range)
Unit
Step
Default
Description
DirModeSel1
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 1 (Off, Non-dir,
Forward, Reverse)
Characterist1
ANSI Ext. inv.
ANSI Very inv.
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
-
-
ANSI Def. Time
Time delay characteristic for step 1
Pickup1
1 - 2500
%IB
1
100
Residual current operate level for step 1 in % of
IBase
t1
0.000 - 60.000
s
0.001
0.000
Def time delay or add time delay for inverse
char of step 1
TD1
0.05 - 999.00
-
0.01
0.05
Time multiplier for the step 1 selected time
characteristic
IMin1
1.00 - 10000.00
%IB
1.00
100.00
Minimum operate residual current for step 1 in
% of IBase
t1Min
0.000 - 60.000
s
0.001
0.000
Minimum operate time for inverse time
characteristic step 1
MultPU1
1.0 - 10.0
-
0.1
2.0
Multiplier for the residual current setting value
for step 1
HarmBlock1
Disabled
Enabled
-
-
Enabled
Enable block of step 1 for harmonic restraint
DirModeSel2
Disabled
Non-directional
Forward
Reverse
-
-
Non-directional
Directional mode of step 2 (Off, Non-dir,
Forward, Reverse)
Table continues on next page
Section 8
1MRK 511 365-UUS A
Current protection
192
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...