Function block
First LON address in
function block
EVENT:4
1072
EVENT:5
1088
EVENT:6
1104
EVENT:7
1120
EVENT:8
1136
EVENT:9
1152
EVENT:10
1168
EVENT:11
1184
EVENT:12
1200
EVENT:13
1216
EVENT:14
1232
EVENT:15
1248
EVENT:16
1264
EVENT:17
1280
EVENT:18
1296
EVENT:19
1312
EVENT:20
1328
Event masks
The event mask for each input can be set individually from Parameter Setting Tool (PST)
under:
Settings/IED settings/ Monitoring / EventFunction
or via parameter setting tool
(PST) as follows:
•
No events
•
OnSet, at pick-up of the signal
•
OnReset, at drop-out of the signal
•
OnChange, at both pick-up and drop-out of the signal
•
AutoDetect, event system itself make the reporting decision, (reporting criteria for
integers has no semantic, prefer to be set by the user)
The following type of signals from application functions can be connected to the event
function block.
Single indication
Directly connected binary IO signal via binary input function block (SMBI) is always
reported on change, no changed detection is done in the event function block. Other
Boolean signals, for example a pickup or a trip signal from a protection function is event
masked in the event function block.
Double indications
Section 18
1MRK 511 365-UUS A
Station communication
624
Phasor measurement unit RES670 2.1 ANSI
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...