21.2.11.5
Monitored data
Table 668:
MIM Monitored data
Name
Type
Values (Range)
Unit
Description
STATUS
BOOLEAN
0=Ok
1=Error
-
Milliampere input module
status
CH1
REAL
-
-
Analog input 1
CH2
REAL
-
-
Analog input 2
CH3
REAL
-
-
Analog input 3
CH4
REAL
-
-
Analog input 4
CH5
REAL
-
-
Analog input 5
CH6
REAL
-
-
Analog input 6
CH1
REAL
-
A
Service value analog input 1
CH2
REAL
-
A
Service value analog input 2
CH3
REAL
-
A
Service value analog input 3
CH4
REAL
-
A
Service value analog input 4
CH5
REAL
-
A
Service value analog input 5
CH6
REAL
-
A
Service value analog input 6
21.2.11.6
Technical data
Table 669:
MIM - mA input module
Quantity:
Rated value:
Nominal range:
Input resistance
R
in
= 194 Ohm
-
Input range
±5, ±10, ±20mA
0-5, 0-10, 0-20, 4-20mA
-
Power consumption
each mA-board
each mA input
£
2 W
£
0.1 W
-
21.2.12
Galvanic RS485 communication module
21.2.12.1
Introduction
The Galvanic RS485 communication module (RS485) is used for DNP3.0 and IEC
60870-5-103 communication. The module has one RS485 communication port. The
RS485 is a balanced serial communication that can be used either in 2-wire or 4-wire
connections. A 2-wire connection uses the same signal for RX and TX and is a multidrop
communication with no dedicated Master or slave. This variant requires however a control
1MRK 511 365-UUS A
Section 21
IED hardware
Phasor measurement unit RES670 2.1 ANSI
795
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...