Name
Type
Default
Description
INPUT6
BOOLEAN
0
Binary input 6
INPUT7
BOOLEAN
0
Binary input 7
INPUT8
BOOLEAN
0
Binary input 8
INPUT9
BOOLEAN
0
Binary input 9
INPUT10
BOOLEAN
0
Binary input 10
INPUT11
BOOLEAN
0
Binary input 11
INPUT12
BOOLEAN
0
Binary input 12
INPUT13
BOOLEAN
0
Binary input 13
INPUT14
BOOLEAN
0
Binary input 14
INPUT15
BOOLEAN
0
Binary input 15
INPUT16
BOOLEAN
0
Binary input 16
Table 265:
INDCALH Output signals
Name
Type
Description
IND
BOOLEAN
OR function betweeen inputs 1 to 16
15.5.5
Settings
Table 266:
INDCALH Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Disabled
Enabled
-
-
Disabled
Operation Disabled/Enabled
15.5.6
Operation principle
The logic for group indication INDCALH block is provided with 16 input signals and 1
IND output signal. The function block incorporates internal logic OR gate in order to
provide grouping of connected input signals to the output IND signal from the function
block.
When any one of 16 input signals (INPUT1 to INPUT16) has logical value 1, the IND
output signal will get logical value 1.
The function has a drop-off delay of 200 ms when all inputs are reset to provide a steady
signal.
1MRK 511 365-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.1 ANSI
427
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...