15.16.2
Functionality
The function gives the possibility to monitor the level of real value signals in the system
relative to each other or to a fixed value. It is a basic arithmetic function that can be used
for monitoring, supervision, interlocking and other logics.
15.16.3
Function block
REALCOMP
INPUT
REF
INEQUAL
INHIGH
INLOW
IEC15000053-1-en.vsdx
IEC15000053 V1 EN
15.16.4
Signals
Table 372:
REALCOMP Input signals
Name
Type
Default
Description
INPUT
REAL
0.000
Input value to be compared with reference value
REF
REAL
0.000
Reference value to be compared with input value
Table 373:
REALCOMP Output signals
Name
Type
Description
INEQUAL
BOOLEAN
Input value is equal to the reference value
INHIGH
BOOLEAN
Input value is higher than the reference value
INLOW
BOOLEAN
Input value is lower than the reference value
15.16.5
Settings
Table 374:
REALCOMP Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
EnaAbs
Signed
Absolute
-
-
Signed
Selection for absolute or signed comparison
RefSource
Set Value
Input REF
-
-
Set Value
Selection for reference value either input or
setting
SetValue
-999.999 - 999.999
-
0.001
0.001
Set value for reference
Table continues on next page
1MRK 511 365-UUS A
Section 15
Logic
Phasor measurement unit RES670 2.1 ANSI
479
Technical manual
Содержание Relion 670 Series RES670
Страница 1: ...Relion 670 series Phasor measurement unit RES670 2 1 ANSI Technical manual ...
Страница 2: ......
Страница 36: ...30 ...
Страница 76: ...70 ...
Страница 106: ...100 ...
Страница 150: ...144 ...
Страница 274: ...268 ...
Страница 326: ...320 ...
Страница 356: ...350 ...
Страница 382: ...376 ...
Страница 416: ...410 ...
Страница 590: ...584 ...
Страница 604: ...598 ...
Страница 694: ...688 ...
Страница 756: ...750 ...
Страница 834: ...828 ...
Страница 836: ...830 ...
Страница 876: ...870 ...
Страница 886: ...880 ...
Страница 887: ...881 ...